Zero Transfer Time UPS - ICONICA 5kW 48V Inverter-Charger and 4x Rolls 3.12kWh 12V AGM Batteries
Zero Transfer Time UPS – ICONICA 5kW 48V Inverter-Charger with 4 × Rolls S12-290AGM 3.12kWh Batteries
- Keep selected equipment powered during a mains outage, with 0ms transfer between line and battery modes when correctly configured.
- Supply up to 5,000W of continuous pure sine wave power from a 48V AGM battery bank.
- Four Rolls batteries provide 12.48kWh nominal storage at C20, with mains charging and an integrated MPPT solar charge controller.
5kW zero transfer time UPS for essential business loads
This zero transfer time UPS combines an ICONICA IC-ZT5000-48 inverter-charger with four Rolls S12-290AGM 260Ah (C20) deep-cycle batteries. Connected in series, the batteries form a 48V, 12.48kWh battery bank for selected essential-load circuits. The inverter accepts mains or a compatible generator supply and can also charge from a correctly designed solar array.
This inverter has the ability to be connected in parallel with additional identical units (maximum of 8 further inverters), offering the possibility of large-scale system expansion, with up to 45kW of power handling capability and up to 112.3kWh battery storage capacity. Once connected in parallel, there is the option for 3-phase operation (ideal if the system is being used to power industrial grade equipment and machinery run on 3 phase). Each inverter connected in the system will require a parallel connection kit (sold separately).
Key features
- Continuity for sensitive equipment: 0ms transfer between line and battery modes. Transfer between inverter and bypass modes is 4ms, so operating-mode configuration matters.
- 5kW pure sine wave output: 5kVA/5kW continuous inverter rating, with twice rated power available for five seconds within the inverter’s operating limits.
- Deep-cycle AGM storage: four 12V batteries, each rated at 260Ah at C20, provide a 4 x 3.12kWh 48V series bank without routine electrolyte topping-up.
- Flexible charging: up to 60A mains charging and an integrated 80A MPPT controller supporting up to 4,000W of compatible solar input.
- Local control and monitoring: removable LCD display, Bluetooth and RS232 communication, with overload, overtemperature and short-circuit protection.
Where to use
Suitable for assessed essential-load circuits serving logistics offices, commercial workstations, network switches, routers, CCTV recorders, access-control equipment and selected small-server installations. Check total running power, starting surges, equipment compatibility and required backup duration before specifying the system.
This package provides a single-phase supply for selected loads, not a complete factory or warehouse backup system. Medical, life-safety and other specialist applications require a separate suitability assessment.
System contents and usable capacity
- 1 × ICONICA IC-ZT5000-48 5kW 48V zero transfer time inverter-charger.
- 4 × Rolls S12-290AGM 12V deep-cycle AGM batteries, each with 3.12kWh nominal energy at C20.
- 1 x Mersen DC Fused Disconnect 2-pole NH1 fuse size 250ADC max
- Required cables, battery interlinks, fuses, AC protection and any enclosure included.
The bank’s 12.48kWh figure is nominal stored energy at the 20-hour discharge rate, not guaranteed usable AC energy. A 50% depth-of-discharge allowance corresponds to 6.24kWh of that nominal figure before inverter losses and discharge-rate effects. Actual runtime depends on load, battery temperature, condition and commissioned cut-off settings.
Installation and commissioning
This is not a plug-in UPS. A qualified electrician must design and install the battery connections, DC protection and isolation, AC protection, earthing and essential-load circuits. Ask Energian about installation through trusted partners.
Install the inverter vertically on a suitable non-combustible surface. Provide a secure, ventilated battery location with sufficient access and structural support: the four batteries weigh 312kg before cables or an enclosure are added.
Set charging voltage, charging-current limits and low-voltage protection for the Rolls batteries and their operating temperature. Do not assume the inverter’s default AGM profile is suitable. Keep battery equalisation disabled and confirm the maximum permitted charging current before enabling simultaneous solar and mains charging.
Technical specifications
Inverter figures use the 5kW column of the supplied IC-ZT user manual, version 1.2. Battery figures follow the supplied S12-290 AGM datasheet. Calculated system figures are identified separately.
| Specification | Value |
|---|---|
| System configuration | |
| Inverter model | ICONICA IC-ZT5000-48 |
| Battery quantity and model | 4 × Rolls S12-290AGM |
| Battery-bank arrangement | Four 12V batteries in series; one 48V string |
| Bank capacity at C20 | 260Ah at 48V |
| Bank capacity at C100 | 290Ah at 48V |
| Bank capacity at C10 | 234Ah at 48V |
| Nominal energy per battery at C20 — calculated | 3.12kWh: 12V × 260Ah |
| Nominal bank energy at C20 — calculated | 12.48kWh: 48V × 260Ah |
| Nominal bank energy at C100 — calculated | 13.92kWh: 48V × 290Ah |
| Nominal bank energy at C10 — calculated | 11.232kWh: 48V × 234Ah |
| 50% of C20 nominal bank energy — calculated | 6.24kWh before inverter losses and discharge-rate effects; not a guaranteed usable-energy rating |
| Battery weight | 78kg |
| Combined inverter and battery net weight — calculated | 325.5kg, excluding cables, protection devices, enclosure and packaging |
| Inverter: AC input and line mode | |
| Input waveform | Sinusoidal |
| Nominal AC input voltage | 230V AC |
| Maximum AC input voltage | 300V AC |
| Low-loss input voltage / return voltage | 110V AC ±7V / 120V AC ±7V |
| High-loss input voltage / return voltage | 280V AC ±7V / 270V AC ±7V |
| Nominal input frequency | 50Hz / 60Hz, automatic detection |
| Low-loss frequency | 46Hz at 50Hz input; ±1Hz |
| Low-loss return frequency | 46.5Hz at 50Hz input; |
| High-loss frequency | 54Hz at 50Hz input; ±1Hz |
| High-loss return frequency | 53Hz at 50Hz input; ±1Hz |
| Power factor | >0.98 |
| Peak line-mode efficiency | 93% |
| Transfer time: line ↔ battery | 0ms |
| Transfer time: inverter ↔ bypass | 4ms |
| Output short-circuit protection | Circuit breaker in line mode; electronic circuits in battery mode |
| Inverter: battery mode and AC output | |
| Rated output | 5kVA / 5kW |
| Output waveform | Pure sine wave |
| Output voltage regulation | 230V AC ±5% |
| Output frequency | 50Hz or 60Hz |
| Peak battery-mode efficiency | 90% |
| Overload protection | 5 seconds at ≥150% load; 10 seconds at 105–150% load |
| Surge capacity | Twice rated power for 5 seconds |
| Nominal DC input voltage | 48V DC |
| DC operating range | 40–66V DC |
| Cold-start voltage | 46V DC |
| Low DC warning voltage | 45V at <50% load; 44V at ≥50% load |
| Low DC warning return voltage | 47V at <50% load; 46V at ≥50% load |
| Low DC cut-off voltage in specification table | 43V at <50% load; 42V at ≥50% load |
| User-defined low DC cut-off setting | 40.0–54.0V in 0.1V increments; must be commissioned for the batteries |
| High DC recovery / cut-off voltage | 64V / 66V |
| No-load power consumption | <75W |
| Inverter: mains and solar charging | |
| Mains charging current at nominal AC voltage | 30A default; 60A maximum |
| Mains charging-current selections | 2A, 10A, 20A, 30A, 40A, 50A or 60A, subject to the total charging-current setting |
| Charging algorithm | Three-stage: bulk, absorption and float |
| Default AGM/GEL bulk voltage | 56.4V DC; inverter preset, not the commissioned Rolls battery setting |
| Default flooded-battery bulk voltage | 58.4V DC; not the battery-type selection for this AGM package |
| Default float voltage | 54V DC; inverter preset, not the commissioned Rolls battery setting |
| User-defined bulk and float voltage ranges | 48.0–64.0V in 0.1V increments |
| Overcharge protection | 66V DC |
| Solar charge-controller type | MPPT |
| Maximum solar input power | 4,000W |
| Maximum solar charging current | 80A |
| Maximum solar-controller efficiency | 98.0% |
| Maximum PV array open-circuit voltage | 145V DC; array design must account for cold-weather voltage rise |
| PV MPPT operating range | 60–115V DC |
| Battery-voltage measurement accuracy | ±0.3% |
| PV-voltage measurement accuracy | ±2V |
| Maximum combined mains and solar charging current | 140A inverter capability; this is not an approved charging-current setting for the supplied battery bank |
| Total charging-current adjustment | 10–140A in 10A increments; 60A default |
| Inverter: ECO/bypass mode | |
| Input waveform | Sinusoidal |
| Low-loss input voltage / return voltage | 176V AC ±7V / 186V AC ±7V |
| High-loss input voltage / return voltage | 280V AC ±7V / 270V AC ±7V |
| Nominal input frequency | 50Hz / 60Hz, automatic detection |
| Low-loss frequency / return frequency | 46Hz / 46.5Hz at 50Hz input; ±1Hz |
| High-loss frequency / return frequency | 54Hz / 53Hz at 50Hz input; ±1Hz |
| Inverter: controls and environment | |
| Display | Removable LCD display with status indicators and function buttons; remote mounting requires an optional communication cable |
| Communication | RS232 and Bluetooth; USB functions for firmware, parameter transfer and data logs |
| Bluetooth monitoring | WatchPower; manual states approximately 6–7m range in open space |
| Dry contact | 3A / 250V AC for external signalling |
| Operating modes | Automatic, online and ECO options; configurable utility-first, solar-first and solar/battery/utility priorities |
| Operating temperature | 0°C to 55°C |
| Storage temperature | −15°C to 60°C |
| Relative humidity | 5–95%, non-condensing |
| Inverter dimensions, D × W × H | 140 × 303 × 525mm |
| Inverter net weight | 13.5kg |
| Rolls S12-290AGM: per-battery specifications | |
| Battery technology | Deep-cycle AGM lead-acid |
| Nominal voltage | 12V |
| Capacity at C100, 25°C | 290Ah |
| Capacity at C20, 25°C | 260Ah |
| Capacity at C10, 25°C | 234Ah |
| Internal resistance | 1.8mΩ, fully charged at 25°C |
| Maximum short-duration discharge | 2,600A for 5 seconds at 25°C; not a continuous operating rating |
| Standard terminal | LT |
| Terminal hole shown in drawing | Ø9mm |
| Battery dimensions, L × W × H | 521 × 269 × 245mm |
| Weight per battery | 78kg |
| Cycle charging voltage at 25°C | 14.5–14.9V DC per battery |
| Float charging voltage at 25°C | 13.6–13.8V DC per battery |
| Four-battery cycle-voltage range — calculated | 58.0–59.6V DC at 25°C; final setting to follow Rolls commissioning guidance |
| Four-battery float-voltage range — calculated | 54.4–55.2V DC at 25°C; final setting to follow Rolls commissioning guidance |
| Capacity at 40°C / 25°C / 0°C / −15°C | 102% / 100% / 85% / 65%, based on the 20-hour rate |
| Capacity remaining after storage at 25°C | 91% after 3 months; 82% after 6 months; 64% after 12 months |
| Reserve capacity at 25A | 530 minutes |
| Reserve capacity at 75A | 130 minutes |
| Cold-cranking rating at 0°C | 1,830A, as labelled in the datasheet; not an inverter continuous-discharge rating |
| Cold-cranking rating at −18°C | 1,525A; not an inverter continuous-discharge rating |
| Battery constant-current discharge data | |
| Discharge-test endpoint | 1.75V per cell: 10.5V per battery, or 42V for the four-battery series string. This is a test endpoint, not a recommended routine operating target. |
| 30-minute discharge current | 233A |
| 45-minute discharge current | 172A |
| 1-hour discharge current | 147.8A |
| 2-hour discharge current | 78.3A |
| 3-hour discharge current | 58.9A |
| 5-hour discharge current | 41.3A |
| 8-hour discharge current | 28.3A |
| 10-hour discharge current | 23.40A |
| 20-hour discharge current | 13.00A |
| Discharge-data interpretation | Battery test figures, not guaranteed system runtimes. The same current flows through all batteries in series; constant-power inverter current increases as bank voltage falls. |
| Installation and battery-care requirements | |
| Battery-bank sizing reference | The inverter manual suggests at least 200Ah for the 5kW model; this package provides 260Ah at C20. |
| Battery enclosure | Secure, accessible and ventilated; do not install the AGM bank in a completely sealed enclosure |
| Battery spacing | Rolls recommends 25–75mm between batteries for airflow and maintenance access. |
| Charging configuration | Verify current limits, absorption duration and temperature-adjusted voltage settings against Rolls guidance and the battery labels. |
| Equalisation | Disabled for AGM batteries |
| Protection and isolation | External battery overcurrent protection, suitable isolation, AC protection and earthing must be designed for the installation. |
| Maintenance safety | Isolate all relevant AC, battery and PV supplies before work. The inverter’s on/off switch alone does not provide safe isolation. |
Documents available for download
- Rolls S12-290AGM datasheet
- ICONICA IC-ZT installation and user manual, including inverter specifications
- Rolls battery installation, charging and maintenance manual
Manual revisions may change. Use the documentation supplied with the equipment and confirm the applicable specifications before installation.
Shipping
Shipping is available to the UK, Ireland, Africa, the Caribbean and worldwide. If a shipping rate is not shown at checkout, contact us on +44 20 8064 0335 or info@energian.co.uk for a quote.
UK expert support
Energian’s UK team can help assess essential loads, backup capacity, solar compatibility and installation requirements. Contact us by phone, email or live chat with questions or support requests, or arrange an in-person consultation at our office.